در حال نمایش 3 نتیجه

نمایش 9 24

ترانسمیتر فشار رزمونت ROSEMOUNT 3051C

GENERAL INFORMATION
Series / Product

Series

Brand

ROSEMOUNT

Origin

USA

Series

ROSEMOUNT – 3051C Coplanar

PRESSURE SENSOR SPECIAL FEATURES
Product Type

Pressure Transmitter

Technology (Measuring Principle)

N/A

Varieties

Absolute, Explosion Proof (EX), Flush Diaphragm, High Accuracy, Vacuum / Compound

MEASURING RANGES
Reference Pressure

Absolute, Differential, Gauge

Pressure Unit

[bar], [mbar], [psi], [inH2O]

Pressure Range

■ Gauge: -62.16 … 62.16 mbar to -0.97 … 137.89 bar ■ Absolute: 0 … 2.06 bar to 0 … 275.79 bar ■ Differential: -7.46 … 7.46 mbar to -137.89 … 137.89 bar

Pressure Range [bar] [Min]

-0.97

Pressure Range [bar] [Max]

275.79

Pressure Range [psi] [Min]

-14.2

Pressure Range [psi] [Max]

4000

Static Pressure [bar] [Max]

N/A

Overpressure [bar] [Max]

N/A

Positive Overpressure [bar]

N/A

Negative Overpressure [bar]

N/A

Burst Pressure [bar] [Min]

N/A

PRESSURE SENSOR PERFORMANCE
Accuracy

≤ ± 0.04 %FS, ≤ ± 0.065 %FS, ≤ ± 0.1 %FS

Accuracy Details

N/A

Non-linearity

N/A

Non-linearity Details

N/A

Long Term Stability

≤ ± 0.15 %URL, ≤ ± 0.2 %URL

Long Term Stability Details

15-year stability

TC Sensitivity

N/A

TC Zero Point

N/A

Adjustable

YES

Adjustability Details

Refer to the datasheet

Resolution

N/A

Sensitivity

N/A

Response Time

< 100 ms, < 255 ms, < 700 ms

Response Time Details

■ Total response time (Dead time+Time constant) ■ 4 – 20 mA HART® (Ranges 2-5: 100 ms, Range 1: 255 ms, Range 0: 700 ms)

ELECTRICAL SPECIFICATIONS
Output Signal

1 … 5 VDC HART®, 4 … 20 mA HART®, FOUNDATION™ Fieldbus, PROFIBUS® PA, Wireless

Output Signal Details

■ 4–20 mA with digital signal based on HART® protocol, Configured for HART Revision 7 ■ FOUNDATION™ Fieldbus protocol

Supply Voltage

N/A

Load Resistance

N/A

Power Consumption

N/A

Short-circuit Protection

N/A

Reverse Polarity Protection

N/A

ENVIROMENTAL CONDITIONS
Media Temperature [°C] [Min]

-60

Media Temperature [°C] [Max]

+149

Ambient Temperature [°C] [Min]

-60

Ambient Temperature [°C] [Max]

+85

Storage Temperature [°C] [Min]

-60

Storage Temperature [°C] [Max]

+85

Compensated Temperature [°C] [Min]

N/A

Compensated Temperature [°C] [Max]

N/A

Ingress Protection

IP66, IP68, NEMA 4X

Vibration Resistance

Less than ±0.1 percent of URL when tested per the requirements of IEC60770-1 field or pipeline with high vibration level (10–60 Hz 0.21 mm displacement peak amplitude/60–2000 Hz 3 g).

Shock Resistance

N/A

GENERAL MECHANICAL SPECIFICATIONS
Mounting

Flush Diaphragm, Threaded – Internal Diaphragm

Process Connection Male/Female

Male

Process Connection

Flange, Valve Manifold

Process Connection Details

N/A

With Damper (Puls-snubber)

NO

Process Connection Material

Hastelloy® C-276 (2.4819), Monel 400® gold-plated, Monel® 400, Stainless steel (316L), Stainless steel (316L) gold-plated, Tantalum

Diaphragm / Sensor Material

Hastelloy® C-276 (2.4819), Monel 400® gold-plated, Monel® 400, Stainless steel (316L), Stainless steel (316L) gold-plated, Tantalum

Filling Fluid

Inert fluid, Silicon oil

Seal

Glass-filled PTFE, Graphite-filled PTFE

Hygienic Version

NO

Electrical Connection

1/2"-14 NPT Conduit entry, G 1/2" Conduit entry, M20x1.5 Conduit entry

Electrical Connection Details

■ M12, 4-pin, male connector (eurofast®) ■ A size mini, 4-pin, male connector (minifast®)

Display

YES

Display Details

■ LCD display with LOI (Only available with 4-20 mA HART output (code A) and PROFIBUS-PA (code W) ■ LCD display

Weight

■ Rosemount 3051 in lb. (kg): 6.0 (2.7) ■ Wireless in lb. (kg): 3.9 (1.8)

TESTS / APPROVALS
Scope Approvals

ATEX / Europe, CSA / Canada, FM / USA, IECEx / Worldwide, INMETRO / Brazil, NACE / International, TIIS / Japan

Ship Approvals

ABS / USA, BV / Global, DNV-GL / Germany, LR / The UK

Explosion Protection

Dust Explosion Protection Through Housing "t", Flameproof Enclosure "d", Intrinsic Safety "i", Non-incendive "n"

EX Zone

Zone 0, Zone 1, Zone 2

Other Approvals

N/A

SIL Qualification

N/A

INDUSTRIES / APPLICATIONS
Application

Calibration & testing labs, Liquid, steam and gas pressure measurement, Oil field equipment, Oil platforms, Pressure monitoring in the hazardous areas, Process technology

ترانسمیتر فشار روزمونت ROSEMOUNT 3051T

GENERAL INFORMATION
Series / Product

Series

Brand

ROSEMOUNT

Origin

USA

Series

ROSEMOUNT – 3051T

PRESSURE SENSOR SPECIAL FEATURES
Product Type

Pressure Transmitter

Technology (Measuring Principle)

Field-proven piezoresistive sensor

Varieties

Absolute, Explosion Proof (EX), High Accuracy, Vacuum / Compound

MEASURING RANGES
Reference Pressure

Absolute, Gauge

Pressure Unit

[bar], [psi]

Pressure Range

■ Gauge: -5 … 5 psi to -14.7 … 20,000 psi / -344.74 … 344.74 mbar to -1.01 … 1378.95 bar ■ Absolute: 0 … 30 psi to 0 … 20,000 psi / 0 … 2.06 bar to 0 … 1378.95 bar

Pressure Range [bar] [Min]

-1.01

Pressure Range [bar] [Max]

1379

Pressure Range [psi] [Min]

-14.7

Pressure Range [psi] [Max]

20000

Static Pressure [bar] [Max]

N/A

Overpressure [bar] [Max]

N/A

Positive Overpressure [bar]

N/A

Negative Overpressure [bar]

N/A

Burst Pressure [bar] [Min]

N/A

PRESSURE SENSOR PERFORMANCE
Accuracy

≤ ± 0.04 %FS, ≤ ± 0.075 %FS

Accuracy Details

Refer to the datasheet

Non-linearity

N/A

Non-linearity Details

N/A

Long Term Stability

≤ ± 0.2 %URL

Long Term Stability Details

10-year stability of 0.2 percent of URL

TC Sensitivity

N/A

TC Zero Point

N/A

Adjustable

YES

Adjustability Details

■ Digital zero trim ■ Turndown: Up to 150:1

Resolution

N/A

Sensitivity

N/A

Response Time

< 100 ms, < 152 ms

Response Time Details

■ 4 – 20 mA HART®: 100 ms ■ FOUNDATION™ Fieldbus and PROFIBUS®PA Protocols: 152 ms ■ Update rate: 22 times per second

ELECTRICAL SPECIFICATIONS
Output Signal

1 … 5 VDC HART®, 4 … 20 mA HART®, FOUNDATION™ Fieldbus, PROFIBUS® PA, Wireless

Output Signal Details

■ HART Revision 5 is the default HART output ■ WirelessHART® ■ Configured for HART Revision 5 ■ Configured for HART Revision 7

Supply Voltage

N/A

Load Resistance

N/A

Power Consumption

N/A

Short-circuit Protection

N/A

Reverse Polarity Protection

N/A

ENVIROMENTAL CONDITIONS
Media Temperature [°C] [Min]

-40

Media Temperature [°C] [Max]

+149

Ambient Temperature [°C] [Min]

-60

Ambient Temperature [°C] [Max]

+85

Storage Temperature [°C] [Min]

-60

Storage Temperature [°C] [Max]

+110

Compensated Temperature [°C] [Min]

N/A

Compensated Temperature [°C] [Max]

N/A

Ingress Protection

IP65, IP66, IP68, NEMA 4X

Vibration Resistance

Less than ±0.1 percent of URL when tested per the requirements of IEC60770-1: 1999 field or pipeline with high vibration level (10– 60 Hz 0.21 mm displacement peak amplitude/60–2000 Hz 3g).

Shock Resistance

N/A

GENERAL MECHANICAL SPECIFICATIONS
Mounting

Threaded – Internal Diaphragm

Process Connection Male/Female

Female, Male

Process Connection

1/2"-14 NPT, F250C (1/4" HP) Autoclave, Flange, G 1/2"

Process Connection Details

N/A

With Damper (Puls-snubber)

NO

Process Connection Material

Hastelloy® C-276 (2.4819), Stainless steel (316) gold-plated, Stainless steel (316L)

Diaphragm / Sensor Material

Hastelloy® C-276 (2.4819), Stainless steel (316L)

Filling Fluid

Fluorinert™ FC-43, Silicon oil

Seal

Glass-filled PTFE, Graphite-filled PTFE

Hygienic Version

NO

Electrical Connection

1/2"-14 NPT Conduit entry, G 1/2" Conduit entry, M20x1.5 Conduit entry

Display

YES

Display Details

■ LCD display with LOI (Only available with 4-20 mA HART output (code A) and PROFIBUS-PA (code W) ■ LCD display

Weight

■ Rosemount 3051 in lb. (kg): 3.0 (1.4) ■ Wireless in lb. (kg): 1.9 (0.86)

TESTS / APPROVALS
Scope Approvals

ATEX / Europe, CE / European Community, EACEx / Eurasian Economic Community, FM / USA, IECEx / Worldwide, INMETRO / Brazil, KCs (KOSHA) / South Korea, NACE / International, NEPSI / China, TIIS / Japan

Ship Approvals

ABS / USA, BV / Global, DNV-GL / Germany, LR / The UK

Explosion Protection

Intrinsic Safety "i" Flameproof Enclosure "d" Non-incendive "n" Dust Explosion Protection Through Housing "t"

EX Zone

Zone 0, Zone 1, Zone 2

Other Approvals

N/A

SIL Qualification

SIL2/3

INDUSTRIES / APPLICATIONS
Application

Calibration & testing labs, Liquid, steam and gas pressure measurement, Oil field equipment, Oil platforms, Pressure monitoring in the hazardous areas, Process technology

ترانسمیتر فشار رزمونت ROSEMOUNT 2088

GENERAL INFORMATION
Series / Product

Series

Brand

ROSEMOUNT

Origin

USA

Series

ROSEMOUNT – 2088

PRESSURE SENSOR SPECIAL FEATURES
Product Type

Pressure Transmitter

Technology (Measuring Principle)

Field-proven piezoresistive sensor

Varieties

Absolute, Explosion Proof (EX), High Accuracy, Vacuum / Compound

MEASURING RANGES
Reference Pressure

Absolute, Gauge

Pressure Unit

[bar], [psi]

Pressure Range

■ Gauge: -14.7 … 30 psi to -14.7 … 4000 psi / -1.01 … 2.1 bar to -1.01 … 275.8 bar ■ Absolute: 0 … 30 psi to 0 … 4000 psi / 0 … 2.1 bar to 0 … 275.8 bar

Pressure Range [bar] [Min]

-1.01

Pressure Range [bar] [Max]

275.8

Pressure Range [psi] [Min]

-14.7

Pressure Range [psi] [Max]

4000

Static Pressure [bar] [Max]

N/A

Overpressure [bar] [Max]

N/A

Positive Overpressure [bar]

N/A

Negative Overpressure [bar]

N/A

Burst Pressure [bar] [Min]

N/A

PRESSURE SENSOR PERFORMANCE
Accuracy

≤ ± 0.065 %FS, ≤ ± 0.075 %FS

Accuracy Details

■ ±0.075% of calibrated span. Includes combined effects of linearity, hysteresis, and repeatability ■ 0.065% accuracy to 10:1 turndown ■ For spans less than 10:1, accuracy = ±[0.009(URL/SPAN)]% span

Non-linearity

N/A

Non-linearity Details

N/A

Long Term Stability

≤ ± 0.1 %FS

Long Term Stability Details

Ranges 2–4: ±0.10 percent of URL for three years Range 1: ±0.10 percent of URL for one year

TC Sensitivity

N/A

TC Zero Point

N/A

Adjustable

YES

Adjustability Details

■ Turndown: 10:1 ■ Zero and span values can be set anywhere within the range limits ■ Including local zero and span adjustments ■ Digital zero trim by Configuration buttons

Resolution

N/A

Sensitivity

N/A

Response Time

< 145 ms

Response Time Details

Total response time: 145 milliseconds Update rate: 22 times per second minimum

ELECTRICAL SPECIFICATIONS
Output Signal

1 … 5 VDC HART®, 4 … 20 mA HART®, NAMUR

Output Signal Details

■ 4–20 mA dc/Digital HART Protocol ■ 1–5 Vdc Low Power/Digital HART Protocol

Supply Voltage

N/A

Load Resistance

N/A

Power Consumption

N/A

Short-circuit Protection

N/A

Reverse Polarity Protection

YES

ENVIROMENTAL CONDITIONS
Media Temperature [°C] [Min]

-40

Media Temperature [°C] [Max]

+121

Ambient Temperature [°C] [Min]

-40

Ambient Temperature [°C] [Max]

+85

Storage Temperature [°C] [Min]

-46

Storage Temperature [°C] [Max]

+110

Compensated Temperature [°C] [Min]

N/A

Compensated Temperature [°C] [Max]

N/A

Ingress Protection

IP66, IP68, NEMA 4X

Vibration Resistance

Less than ±0.1 percent of URL when tested per the requirements of IEC60770-1 field or pipeline with high vibration level (10–60 Hz 0.21 mm displacement peak amplitude/60–2000 Hz 3g).

Shock Resistance

N/A

GENERAL MECHANICAL SPECIFICATIONS
Mounting

Threaded – Internal Diaphragm

Process Connection Male/Female

Female, Male

Process Connection

1/2"-14 NPT, Diaphragm seal, G 1/2", M20x1.5, PT 1/2", RC 1/4", Valve Manifold

Process Connection Details

N/A

With Damper (Puls-snubber)

NO

Process Connection Material

Hastelloy® C-276 (2.4819), Stainless steel (316L)

Diaphragm / Sensor Material

Hastelloy® C-276 (2.4819), Stainless steel (316L)

Filling Fluid

Inert fluid, Silicon oil

Seal

Buna-N®

Hygienic Version

NO

Electrical Connection

1/2"-14 NPT Conduit entry, G 1/2" Conduit entry, M20x1.5 Conduit entry

Electrical Connection Details

½–14 NPT, M20 x 1.5 (CM20), or G½ female (PF ½ female) conduit entry

Display

YES

Display Details

■ Fully configurable LCD display to display process variable, percent of range, and diagnostic messages ■ LCD display with local operator interface ■ LCD display, configured for engineering units

Weight

Output code S and N: approximately 2.44 lb (1.11 kg)

TESTS / APPROVALS
Scope Approvals

ATEX / Europe, CE / European Community, Drinking Water System Components / NSF, EACEx / Eurasian Economic Community, FM / USA, HART | FieldComm Group / USA, IECEx / Worldwide, INMETRO / Brazil, KCs (KOSHA) / South Korea, NACE / International, NEPSI / China, TIIS / Japan

Ship Approvals

ABS / USA, BV / Global, DNV-GL / Germany, LR / The UK

Explosion Protection

Dust Explosion Protection Through Housing "t", Flameproof Enclosure "d", Intrinsic Safety "i", Non-incendive "n"

EX Zone

Zone 0, Zone 1

Other Approvals

N/A

SIL Qualification

N/A

INDUSTRIES / APPLICATIONS
Application

Calibration & testing labs, Liquid, steam and gas pressure measurement, Oil field equipment, Oil platforms, Pressure monitoring in the hazardous areas, Process technology